SUPREME XT |
Standard Features
• UL 864
• Three detection zones as standard
• Any single zone or any combinations of zones can be configured to release
• Configurable first stage NAC delays
• Configurable detection delays
• Zero time delay upon manual release option
• Non-latching zone input option to receive signals from other systems such as aspirating equipment
• Configurable releasing delays up to 60 seconds in 5 second steps
• Configurable releasing duration up to 5 minutes in 5 second steps
• Countdown timer shows time remaining until release
• Supports up to seven, four wire status indicators
• Built in Extract Fan control
• Compatible with conventional detectors from Apollo, Hochiki America, and System Sensor
Ordering Codes |
AS1810-10 | Supreme XT – Red 120V |
AS1810-11 | Supreme XT – Red 240V |
AS1810-40 | Supreme XT – Gray 120V |
AS1810-41 | Supreme XT – Gray 240V |
Technical Specifications |
AC Supply | 120V or 240V |
AC Supply Fuse | 3.15A (F3.15A L250V) |
Finish | Epoxy powder coated |
Color | Red (optional gray) |
Power Supply Rating | 3 Amps total including battery charge 28V ± 2V |
Maximum Ripple Voltage | 200 millivolts |
Battery Type | Two 12 Volt 7Ah sealed lead acid in series |
Battery Charge Voltage | 27.6VDC nominal (temperature-compensated) |
Battery Charge Current | 0.7A maximum |
Battery Fuse | 20mm, 3.15A glass Sloblow |
Maximum Current Draw from Batteries | 3A |
Quiescent Current of Panel in Power Failure | 0.095A |
AUX 24V Output | Fused at 500mA with electronic fuse |
NAC Outputs | 24V Fused at 500mA with electronic fuse |
Trouble Relay Contact Rating | 30VDC 1A Amp maximum |
Fire Relay Contact Rating | 30VDC 1A Amp maximum |
Local Fire Relay Contact Rating | 30VDC 1A Amp maximum |
First Stage Contact Rating | 30VDC 1A Amp maximum |
Second Stage Contact Rating | 30VDC 1A Amp maximum |
Extract Contact Rating | 30VDC 1A Amp maximum |
Zone Quiescent Current | 2mA maximum |
Terminal Capacity | 12 AWG |
No. of detectors per zone | Dependent on type (maximum 32) |
Detection circuit end of line | 6K8 5% ½ Watt resistor |
Supervised input end of line | 6K8 5% ½ Watt resistor |
Extinguishant output EOL | 1N4004 Diode |
No. of detection circuits | 3 |
No. of sounder circuits | 2 x 1st Stage, 1 x 2nd Stage |
Extinguishant release output | Rated at 1 Amp |
Extinguishant release delay | Adjustable 0 to 60 seconds (in 5 second steps) |
Extinguishant release duration | Adjustable 60 to 300 seconds (in 5 second steps) |
Normal Zone Impedance (EOL) | 6.8K |
Detector Alarm Impedance | 470 Ohms |
Pull Station Alarm Impedance | 270 Ohms |
Short circuit threshold | Short circuit Impedance 99 Ohms |
Supervised Inputs Normal Impedance (EOL) | 6.8K |
Supervised Inputs Alarm Impedance | 470 Ohms |
Supervised inputs Short circuit threshold | 99 Ohms |
Status unit/Ancillary board connection | Two wire RS485 connection |
Status unit power output | Rated at 500mA with electronic fuse |