SUPREME| Analog Addressable Fire Control PanelsAS1420-10 (2 Loop)AS1440-10 (4 Loop) |
Standard Features
• UL 864 9th Edition listed
• Multi-Loop 2 Analog Addressable Loops Field upgradable to 4
• 127 primary points per loop
• Powerful, network wide cause and effects (500 total)
Fully user programmable by point or zone.
• Up to 800 points per panel when using devices and sub-points
• Up to 10,000 feet wiring length on SLC loop
• 64 Panels on a network
• Programmable through a PC connection
to the panel, or through keypad
• Programmable on-board relays – 5
• Supervised Powered Outputs – 3
• Programmable Notification Appliance Circuits: 4
• Power per NAC: 1.6 Amps Max
• Programmable outputs on SLC loop
• Programmable Function button on front display
• Fire Drill button on front display
• Day and night sensitivity settings (user programmable)
• Power Supply: 5.25 Amp, regulated & integrated
• LCD Display: 8×40
• Zonal Mode: Annunciation by zone w/o individual relationships
• Panel Ring Modes: Common, Zonal, Stage 2
• NAC Outputs programmable as Continuous, March, Temporal
• Program Cause and Effects AND, OR, or Any Two (Cross Zone)
• Battery size: Up to 17 Ah in standard enclosure;
up to 52 Ah with external cabinet
• Access levels: 3
• Access key switch: Yes
• Recognized for use in High Rise
• One man walk test – Fire Test Mode
• Available with semi flush trim ring
• Available in Red or Gray
There are no reviews yet.