Supervised Output Modules (Class A Wiring) |
Standard Features
• Built-in SCI circuitry (VF6041-00 only)
• Flexible application
• Quick response to emergency conditions
• Operation parameters are maintained by the module, and individual communication with the control system during emergency conditions is not required
• Contacts are rated 2.0 Amps @ 24VDC
• Programming is highly flexible providing 16 priority states plus zoning capability
• Programmed device output is turned off, silenced, or programmed to output the selected pattern
Technical Specifications |
Supply Voltage Nominal | 25.3-39 VDC |
Auxiliary Supply Voltage | 24 VDC |
Average Current Consumption | VF6040 420μA (Typical) VF6041 220μA (Typical) On S-SC Line Maximum 6mA (Alarm) |
Current Consumption on Auxiliary Power Lines | 50μA (typical) |
SCI on Resistance | 40 ohm max (normal condition) |
SCI Fault Detection Threshold | 12 Volts (typical) |
SCI Isolation Current (short circuit condition) | 10mA (typical) |
Maximum Quantity per Loop | 127 |
Mounting | 4” Square Electrical Box |
Maximum Humidity | up to 90%, non-condensing |
UL Ambient Installation Temperature Range | 32º F to 120º F |
Dimensions | 4.2” W x 4.7” H x 1.4” D |
There are no reviews yet.