Fast Response Contact Modules |
Standard Features
• Single input contact monitor
• Fast, reliable contact monitoring utilizing the DCP (Digital Communications Protocol)
• 127 devices can be used per DCP loop
• Can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts
• Operates on Class A or Class B SLC loop
• Accepts up to 14 AWG wire
Technical Specifications |
Supply Voltage (S-SC) | 25.3-39 VDC |
Average Current Consumption | 339 μA (typical) 358 mA (Alarm) |
Programmable Input | 1 Monitoring Input |
EOL Device | 10K Ohms Resistor |
Maximum Quantity per Loop | 127 |
Mounting | 2” Electrical Box |
Maximum Humidity | up to 90%, non-condensing |
UL Ambient Installation Temperature Range | 32º F to 120º F |
Dimensions | 1.75” W x 2.37” H x 0.5” D |