Fast Response Contact Module |
Standard Features
• Fast, reliable contact monitoring utilizing the VES DCP (Digital Communications
Protocol)
• 127 devices can be used per DCP loop
• Single input contact monitor
• Can be programmed to monitor Normally Open (NO) or Normally closed
(NC) contacts
• Operates on Class A or Class B SLC loop
Technical Specifications |
Supply Voltage (S-SC) | 25.3 – 39 VDC |
Average Current Consumption | 550µA (Standby) 660µA (Alarm) |
Programmable Input | Monitoring Inputs |
EOL Device | 10K Ohms Resistor |
Maximum Quantity per Loop | 127 |
Maximum Humidity | up to 90%, non-condensing |
Operating Temperature | 32ºF – 120ºF (0ºC – 49ºC) |
Mounting | Single gang electrical box |
Dimensions | 3.0”(W) x 1.9”(H) x 0.5”(D) |
There are no reviews yet.