6” Analog Sounder Base |
Standard Features
• Programmable evacuation codes – Continuous, March, ANSI Temporal patterns
• Base learns the sensor address and assumes
an upper range address (128-254)
• Up to 127 sensors and 127 AS7008s can be used on one SLC loop
• Can be alarmed or reset by zone or by individual address
• SLC loop wire resistance = 50 ohms Max. (total SLC wire run length)
• High sound pressure level (85dB SPL at 10 feet)
Number of Bases Permitted | |
# Bases in | Max. Auxiliary 24VDC Power |
10 | 18.3 ohm |
15 | 12.2 ohm |
20 | 9.1 ohm |
30 | 6.1 ohm |
50 | 3.6 ohm |
60 | 3.0 ohm |
75 | 2.4 ohm |
127 | 1.4 ohm |
NOTE SLC maximum resistance is 50 ohms. |