Bộ cài đặt địa chỉ VF9000-00

The Hand Held Programmer is designed for use with all analog sensors and modules.

Address Setting
1. Install sensor onto programmer, ensuring that sensor protrusions align with programmer grooves.
2. Press the left gray button to switch programmer on. A battery check message will appear followed by the device’s address (Unprogrammed sensors will read address 127).
3. Set the required address by incrementing the left and right gray buttons (the display will show three red flashing dots if the address being programmed is different from the device’s current address).
4. When the desired address is present, press the blue button to store that address. The three red dots on the display will no longer be present.

⇓ Tải xuống Catalogue VF9000

Danh mục:

Handheld Programmer
VF9000-00       


Standard Features
• Compact unit
• Easy to use
• Provides address setting and reading
• Can be used on both sensors and modules
• Has the diagnostic ability to display the analog value
• Over 8000 address settings from one battery

Technical Specifications

Rated Voltage 9 VDC
Battery 9 VDC
Weight 0.34 lbs
Length 6 ¼
Color White

Display Messages

bAt On upon power up (battery check). Also on when battery is low. Low
battery good for up to 3,000 address setting operation.
E0 Attempting to set an address beyond 127
E1 Attempting to program an address with no device connected
E2 Cannot find device after power up
E3 Invalid sensor response
E4 Cannot find the device program
E5 Device read error
E6 Fail during analog value reading

There are no reviews yet.

Be the first to review “Bộ cài đặt địa chỉ VF9000-00”